Home
 
M3460R Voltage Regulator Bonitron > Products > Undervoltage > VDC Regulators > M3460R

The Bonitron M3460R Voltage Regulator protects variable frequency drives from 3-phase, 50% AC line sags. For ratings below 50kW, see the M3534R Voltage Booster.

Bonitron Short Term Sag Solutions, including the M3460R, solve nearly 95% of power quality events. There is no energy storage so the unit is smaller and costs less than traditional UPS systems. Bonitron M3460R Modules are for 3-phase sags and require virtually no maintenance. The M3460R Boost Regulator regulates the DC bus during a voltage sag. As the incoming voltage level drops, the Boost Regulator boosts the rectified DC up to the level needed by the drive.

Bonitron's Ride-Thru Solutions allow your VFDs to meet or exceed:

  • SEMI-F47
  • Samsung Power Vaccine
  • IEC 61000-4-34

M3460R units can be retrofitted with energy storage if future needs require full outage protection.



  • 50% sag protection
  • Hooks directly to drive DC bus connections
  • Parallel connection for increased reliability
  • On-line test without impacting process
  • No batteries or storage necessary
  • Small footprint
  • Increased process availability


 

System Power
(kW)
DC Bus Current
(A)
M3460R Ride-Thru Module Selection
Master Model Number Dimensions
(H x W x D)
Weight
(lbs)
(Quantity)
Slave Model Number
Dimensions
(H x W x D)
Weight
(lbs)
230 - 240VAC Systems  
25 90 M3460R-L025-R10 28.00 x 16.00 x 14.00”  90 N/A
38 133 M3460R-L038-R10
50 178 M3460R-L050-R9 34.00 x 16.00 x  14.00”  120
75 267 M3460R-L075-R11 44.00 x 16.00 x 14.00”  195
100 356 M3460R-L100-R11
125 445 M3460R-L125-R11
135 481 M3460RM-L135-C2 14.50 x 12.50 x 5.00"       15 (2) M3460RS-L075-R11 44.00 x 16.00 x 14.00”  (each) 390
180 641 M3460RM-L180-C2 (2) M3460RS-L100-R11
220 801 M3460RM-L220-C2 (2) M3460RS-L125-R11
260 961 M3460RM-L260-C2 (3) M3460RS-L100-R11 585
330 1202 M3460RM-L330-C2 (3) M3460RS-L125-R11
350 1282 M3460RM-L350-C2 (4) M3460RS-L100-R11 780
440 1602 M3460RM-L440-C2 (4) M3460RS-L125-R11
550 2003 M3460RM-L550-C2 (5) M3460RS-L125-R11 975
650 2403 M3460RM-L650-C2 (6) M3460RS-L125-R11 1170

 

 

System Power
(kW)
DC Bus Current
(A)
M3460R Ride-Thru Module Selection
Master Model Number Dimensions
(H x W x D)
Weight
(lbs)
(Quantity)
Slave Model Number
Dimensions
(H x W x D)
Weight
(lbs)
380 - 415VAC Systems
43 90 M3460R-E043-R10 28.00 x 16.00 x 14.00”  90 N/A
65 133 M3460R-E065-R10
85 178 M3460R-E085-R9 34.00 x 16.00 x  14.00”  120
125 267 M3460R-E125-R11 44.00 x 16.00 x 14.00”  195
165 356 M3460R-E165-R11
205 445 M3460R-E205-R11
225 460 M3460RM-E225-C2 14.50 x 12.50 x 5.00"       15 (2) M3460RS-E125-R11 44.00 x 16.00 x 14.00”  (each) 390
300 610 M3460RM-E300-C2 (2) M3460RS-E165-R11
370 765 M3460RM-E370-C2 (2) M3460RS-E205-R11
450 920 M3460RM-E450-C2 (3) M3460RS-E165-R11 585
560 1150 M3460RM-E560-C2 (3) M3460RS-E205-R11
600 1225 M3460RM-E600-C2 (4) M3460RS-E165-R11 780
750 1530 M3460RM-E750-C2 (4) M3460RS-E205-R11
950 1910 M3460RM-E950-C2 (5) M3460RS-E205-R11 975
1100 2300 M3460RM-E1100-C2 (6) M3460RS-E205-R11 1170

 

 

System Power
(kW)
DC Bus Current
(A)
M3460R Ride-Thru Module Selection
Master Model Number Dimensions
(H x W x D)
Weight
(lbs)
(Quantity)
Slave Model Number
Dimensions
(H x W x D)
Weight
(lbs)
433 - 480VAC Systems
50 85 M3460R-H050-R10 28.00 x 16.00 x 14.00”  90 N/A
75 127 M3460R-H075-R10
100 170 M3460R-H100-R9 34.00 x 16.00 x  14.00”  120
150 255 M3460R-H150-R11 44.00 x 16.00 x 14.00”  195
200 340 M3460R-H200-R11
250 425 M3460R-H250-R11
270 460 M3460RM-H270-C2 14.50 x 12.50 x 5.00"       15 (2) M3460RS-H150-R11 44.00 x 16.00 x 14.00” (each)  390
360 610 M3460RM-H360-C2 (2) M3460RS-H200-R11
450 765 M3460RM-H450-C2 (2) M3460RS-H250-R11
540 920 M3460RM-H540-C2 (3) M3460RS-H200-R11 585
680 1150 M3460RM-H680-C2 (3) M3460RS-H250-R11
720 1225 M3460RM-H720-C2 (4) M3460RS-H200-R11 780
900 1530 M3460RM-H900-C2 (4) M3460RS-H250-R11
1100 1910 M3460RM-H1100-C2 (5) M3460RS-H250-R11 975
1345 2300 M3460RM-H1300-C2 (6) M3460RS-H250-R11 1170

 

 

Options
M3460R Options
DD3 Digital Diagnostic Display with Dual Bargraph Metering and Isolated Status Contacts          
D Dual Output
F AC line and DC link Fusing
K Kinetic Buffrering Bypass
S SCR Input Rectifier - Standard on Multiple Backplate Systems
M3460RS Slave Options
F AC line and DC link Fusing
S SCR Input rectifier

 


Made in the United States of America